Indoor Battery Cabinet + Turnkey Solution
The indoor solution employs a 48V/100Ah solid-state battery system, enabling flexible battery capacity scaling and featuring comprehensive system monitoring and protection. It delivers stable, reliable performance and, when integrated with the air-conditioning system, helps reduce base station operating costs and lower emissions.
Keywords:
Indoor Battery Cabinet + Turnkey Solution
Category:
Base station products
Indoor Battery Cabinet + Turnkey Solution
Product Features
The indoor solution employs a 48V/100Ah solid-state battery system, enabling flexible battery capacity scaling and featuring comprehensive system monitoring and protection. It delivers stable, reliable performance and, when integrated with the air-conditioning system, helps reduce base station operating costs and lower emissions.
Battery specifications
| Serial number | Project | Regular parameters | Note |
| 1 | Model number | QT-48100-16S2P | |
| 2 | Exterior color | Black (RAL 9005) | |
| 3 | Number of series connections | 16S2P | 32 cells, each rated at 3.2 V and 50 Ah, configured in a 16-series, 2-parallel arrangement. |
| 4 | Rated voltage | 51.2V | |
| 5 | Operating voltage range | 40V-58.4V | |
| 6 | Rated capacity | 100Ah | 1/3C discharge to 40 V at 25°C |
| 7 | Discharge termination voltage | 43.2V | |
| 8 | Charging voltage | 56.8V~58.4V | |
| 9 | Discharge cut-off voltage | 40V | |
| 10 | Maximum charge and discharge current | 100A | |
| 11 | Maximum charging current | 100A | Exceeds 50 A; current limiting activated. Current limit value. 10A. Recommended charging current ≤ 0.2C |
| 12 | Self-discharge rate | ≤2%/month | |
| 13 | Operating temperature range (≤95%R.H.) | Operating ambient temperature: -20°C to 45°C Charging at 0℃~55℃ Discharge at -20℃ to 65℃ | Below -10°C, we recommend selecting the heating film option. |
| 14 | Storage temperature range (≤95% R.H.) | -20℃~60℃ | |
| 15 | Transport temperature range | -20℃~60℃ | |
| 16 | Positive and negative terminal lead-out method | Terminal block | |
| 17 | Protection function | Overcharge, overdischarge, short circuit, overload, overheating, etc. | |
| 18 | Battery dimensions (length × width × height) | (480mm*442mm*177mm)±2 | |
| 19 | Battery pack weight | 42±0.5 kg | |
| 20 | Recommended charging method | Constant Current–Constant Voltage–Float Charging | CC:0.2C to 56.4V CV:56.4V Floating:55.2V |
| 21 | Fire safety | Independent thermal‑sensing aerosol devices are installed inside the lithium‑battery pack, enabling automatic fire suppression and safety protection. | |
| 22 | Protection rating | IP20 | |
| 23 | Usage Scenarios | Indoor or outdoor cabinet | Outdoor rainproof and waterproof area |
| 24 | Cycle life | At an ambient temperature of 25°C, with the battery pack operating at 80% depth of discharge (DOD), charged at 0.2C and discharged at 0.2C, the cycle life is ≥3,200 cycles. | |
| 25 | Parallel operation function | Power paralleling port, communication paralleling port, maximum Supports expansion to 15 units. | |
| 26 | Indicator light | 4 battery indicator lights, green; 1 is running. One green indicator light and one red protection light. | |
| 27 | DIP switch | The battery is equipped with a 4-bit DIP switch, allowing you to set the battery pack’s address. | |
| 28 | Switch | Press and hold for 2–3 seconds to power on. Press and hold for 3–6 seconds to power off. | When communication or charging current is present, the battery powers on automatically. Under normal conditions, to shut down, first remove the battery from the system and then press and hold the power button for 3 seconds. |
Previous page